System was in off mode upon arrival. Turned thermostat to cooling mode to perform test. Indoor unit blower came on as it should. Inspect3d outdoor unit and found that fan on top is spinning, but compressor is not. Found that 45/5uf dual run capacitor is reading at 0/2.5uf. Compressor is not getting proper power for operation. Replaced failed capacitor with new 45/5uf capacitor and test run operation. System cam on, both fan and compressor, and suction line got cold. Did not check refrigerant as there is no issues suspected at this time. System is operating in cooling at this time.