Furnace control board 5 amp fuse blown causing shutdown of all 24v control voltage Trace short to outdoor unit starting relay coils Install two pole 30 amp contactor Replace 15 ft of UV damaged control wire between house and outdoor unit Run test equipment in cooling mode from the thermostat controls Air filter is acceptable Supply temperature is 61