Job Checkin

Return in 30 to 60 days from original injection / recharge to perform a full system ultraviolet dye leak search and running refrigerant pressure test. Includes electronic leak test if necessary 7-29-25 Indoor evaporator A-coil inspection and UltraViolet dye leak search validates NO UV Dye visible or leaks detected at today's visit. Running refrigerant pressure test confirms full saturation of the evaporator coil to a 12° sub cooling temperature with 20° super heat based on 78 indoor dry bulb Outdoor system running refrigerant pressure test is perfectly within the specs at 10+1.5° sub cooling at 318psi Supply temperature is stable at 54.8 No suspicion of any future refrigerant leaks at this time.