Thermostat displayed error for running an extended period of time and temperature raising. Homeowner keeps stat at 69 and outdoor was reaching mid 90s. Unit cannot cool beyond approximately 20° outdoor air temperature per design and will likely run nonstop under those conditions. Unit is cooling properly with adequate refrigerant pressures and temperature drop. Informed homeowner how to use Daikin remotes and clean filters and outdoor coils.