Upon arrival inspected unit and found furnace setup moving high cfm doing low dehumidification. Adjust furnace settings to lower cfm for air conditioner bringing higher temperature drop, allowing unit to work faster and more efficiently dehumidifying. Thermostat occasionally goes into error state where it is blank and then says system wait once coming back. “System wait” is normal for any initial power up on the system. The thermostat should not be randomly going blank, adjusted wet switch to verify it stays dry unless drain errors are truly present. As well as adjust humidifier wiring to prevent any low voltage interference for thermostat. If problem persists unit may have a faulty thermostat or wet switch. Ss2 is the double locking tabs bucket style.