2019 carrier 13 seer 2.5 ton r410a cooling system was in desperate need of regular maintenance and cleaning and minor repair parts upon arrival today. The cased evaporator coil and all supply ducks in the mechanical room of the basement are sweating and condensating excessively due to restricted airflow on the indoor unit from a Honeywell 4-in filter installed backwards and sucked off the retainer screening, a heavily matted over and clogged up outdoor condenser coil, and a outdoor unit 370 volt power supply extremely below the specs. (40+5 @ 26+3.5) All contributing to very poor performance of the cooling system Install replacement air filter already on site and labeled the air cleaner with the proper air flow direction. Inspected the evaporator coil and confirmed 90 plus percent condensating. Confirm correct lower speed Water flush outdoor unit condenser coils and run test equipment and cooling mode. System refrigerant pressures are over specs at 15 subcooling however the true and