Cooling preventative maintenance performed Check filter - 16x25x1 filter Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 39.3+5.0 Check OD fan Amp - 0.62 Check compressor Amp - 8.10 Verify pressures and HP-SC/LP-SH 349-13/133-13 Delta T - 17° The Air handler and AC are in optimal running conditions.