Service warranty Upon arrival the system was completely shut down with no blower or geothermal operation for the second floor split system located in the Attic. Thermostat is calling for cooling but reading 86 indoor temp. Attic equipment inspection discovered a tripped off water safety switch in the air coil overflow pan. No water is currently present but has most likely evaporated due to 115° in the attic space. Repositioned safety switch 3/8 inch off the bottom of the pan and out from underneath the line set Recently installed line set insulation is separating from the double-sided tape. (Possible condensation points). Resecured all line set replacement armaflex Cooling system run test from thermostat confirms 20° cooling delta t from 90ra to 70sa Homeowner is resetting temperature on thermostat to 78