Performed cooling maintenance on a Goodman system 14x20x1 filter is OK, change after another month or two Blower OK Blower speed too high, bumped it down one speed lower from factory high setting Outdoor coil 50% plugged with pollen Removed top from unit, washed coil from inside-out Capacitor tested good Wiring in good shape Refrigerant charge OK System operating normally at this time