725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Job Locations
for westerville, oh


Map of Westerville OH
seth p.

seth p.


Job Checkin

Upon arrival today the system was running and at the set temperature of 74 but had partial ice on the evaporator coil and a suction pressure of 84 PSI with 54 superheat and 10° cooling delta t from 76 to 66 The refrigerant charge and UltraViolet dye leak stop that was injected on July 16th 2025 has leaked out to a point that it is no longer cooling the house The ultraviolet dye and refrigerant oil is very easily visible throughout the entire condensation drain system leaking from the evaporator coil. The actual source of the oil and dye leak could not be pinpointed due to the compact design of the equipment however there is no other components in the vicinity. The indoor air coil needs replaced Recharge 2 lb recycled r410a to achieve 119 PSI suction with 17 superheat for temporary cooling until a new Air coil can be installed Seth will contact Bard GeoTec and prepare an estimate for repairs as soon as possible