Upon arrival inspected unit and found unit not fully operating outside. Run capacitor tested at 37.67 for compressor circuit during maintenance. Bottom line for recommendation of replacement. I didn’t suggest replacement during visit had not noticed with the number being so close to ok. Replaced run capacitor with 40+5 today and test run cooling. Unit is back up and operational with 18° delta T