2017 Bryant evolution communicating furnace and thermostat with single stage non-communicating air conditioner Initial cooling system test running will not turn on 24v condenser or initiate proper blower speeds for cooling mode Bryant evolution communicating thermostat will run the air conditioner in cooling mode in service test mode and will produce 51° supply temperature confirming all of the equipment, aside from the communicating thermostat controls, are functioning properly Power cycle and reboot evolution control, confirm online connection for system automatic updates, cycle through equipment fault codes, return equipment to normal operation. Thermostat and equipment is running correctly in cooling mode at this time however homeowners have expressed concern about the humidifier operation which coincides with multiple years of service codes stating failed humidity sensor on the evolution control. Recommend upgrading the Bryant evolution touch screen communicating thermosta