EDMON 630am Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 9 GAL & (1) ANSUL 3 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 9 Gallon: Exhaust fan shuts off when systems were tested, electrician needed to properly interlocked fan to Ansul systems (An9 & An3)