7668 Standish Place
Rockville, MD 20855
(301) 861-0972

Our Top Cities


Job Locations
for washington, dc


Map of Washington DC
Dwayne  B.

Dwayne B.


Job Checkin

EDMON 630am Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 9 GAL & (1) ANSUL 3 GAL Alarm Int: Yes Inoperable Deficiency for Ansul R-102 9 Gallon: Exhaust fan shuts off when systems were tested, electrician needed to properly interlocked fan to Ansul systems (An9 & An3)