jenifer space Kitchen Suppression Inspection Semiannual Inspection Dept: KITCHEN Equip Desc: (1) ANSUL 12 GAL/(2) ANSUL 3 GAL/(2) ANSUL 9 GAL Alarm Int: Yes Deficiency for Ansul R-102 9 Gallon Braising hood: Ansul 9: gallon: wok hood System due for hydro testing MFD 2008 3 hydro tested (3 gallon) cylinders needed Duel cartridge due for 12 year replacement MFD 2008 REGULATOR TEST DUE 3 New regulator hoses needed Deficiency for Ansul R-102 12 Gallon Main hood: Ansul 12 gallon System due for hydro testing 4 hydro tested (3 gallon) cylinders needed 2 duel cartridges are due for 12 year replacement MFD 2008 2 regulators are due for testing 4 new regulator hoses needed Deficiency for Ansul R-102 9 Gallon Wok hood: Ansul 9 gallon “BRAISING HOOD” 3 (3 gallon) cylinders are due for hydro testing MFD 2008 Duel cartridge due for 12 year replacement MFD 2008 Regulator test due 3 new regulator hoses needed Deficiency for Ansul R-102 3 Gallon Pizza hood: Ansul 3 gallon Pizza/ fryer hood