Performed a two system cooling maintenance on two 2019 Trane’s the ODT is 66°.Tested overall operation of equipment confirming the indoor & outdoor equipment was both fully operational.There is two 16x20x1 which were discolored but not clogged each filter was replaced on this visit.Blower motor was fully operational not showing any signs of being intermittent or dropping out.Blower wheel & indoor evaporator coil was inspected finding neither to be dirty.Inspected wires and connections not finding any broken, damaged or arced wires along with didn’t find any damaged or loose connections.Drain line was blew out and flushed confirming proper drainage and condensate pump was cycled as well confirming successful cycle.Flood prevention was tested confirming its operation.Armaflex was damaged in various areas a quote to replace has been provided Once finished evaluating the indoor equipment began evaluating the outdoor equipment checked capacitor, fan amps, compressor amps, refrigerant levels