Customer stated that he replaced filter 2 weeks ago. He said the filter was disgusting. He then turned unit back on and it still froze. He then turned unit. Off. The reason it froze was due to clogged filter, the coils did not have time to thaw after filter was replaced. The unit has been off for 2 weeks so coils have defrosted. Cutting unit on today the pressures are good and temperature drop is good. Advised it will take a while to cool house due to temperature in house.
Increased 6” duct to 8” duct. Fixed bypass damper so air will flow properly. Put screw in supply vent in bedroom.
Need to increase 6” supply duct from damper on the left of the supply plenum to an 8” to the wall stack
Identified failed capacitor 70 + 5, replaced capacitor and tested system. Functions as designed. Compressor amp draw 16.2, RLA 25.0. Fan amp draw 1.3, RLA 1.6