Arrived to complete startup Pulled vacuum down to 183 microns, conducted decay test, system held at 268 microns. Released charge into system and secured service valves. Installed thermostat and Redlinked with indoor unit. Completed thermostat setup. Tested system. Functions as designed. Left thermostat in Off mode