4720 Industrial Access Rd.
Douglasville, GA 30134
770-445-8923

Job Locations
for college park, ga


Map of College Park GA
Rob  S.

Rob S.


Job Checkin

Identified failed zone board and low refrigerant levels. Evaporator was found to be leaking on 20 Jul 22. Technician added 3 lbs of refrigerant. Subcool is currently at .5 *. Superheat at 23*. Zone board isn’t communications to zone dampers to open. Both dampers wet closed when I opened ducts, both zones were calling for cool. Homeowner request quote to replace evaporator, zone board and (2) 12 in zone dampers