Arrived today due to 2017 Carrier not cooling/freezing which is responsible for the upstairs.Upon arrival thermostat was at 76° with a desired temperature of 70° confirmed the indoor & outdoor equipment were both fully operational.Once operation was confirmed began diagnostic on the indoor equipment the filter 20x25x1 was gently used with minimum discoloration the filter wasn’t replaced.Blower motor was fully operational not showing any signs of being intermittent or dropping out.Blower amps were checked finding them to be elevated indicating the motor has been placed under distress which cause some kind of damage.Capacitor was tested confirming it was in specifications.Blower wheel & indoor evaporator coil was inspected finding minimum discoloration but no clogging recommend having monitored to know when cleaning is necessary.Drain line was blew out/flushed confirming it was t clogged and properly draining.Flood prevention was tested confirming it was properly operating.Once finished