Arrived today due to 2017 Goodman having reports of concern of equipment leaking refrigerant the ODT is 66°.Upon arrival thermostat was at 69° with a desired temperature of 70° lowered temperature on thermostat to allow diagnostic confirming the indoor & outdoor equipment was fully operational.Once operation was confirmed began diagnostic on the indoor equipment the filter 16x25x1 was not installed along with no filter rack was installed duct-board was freely cut and not in-closed a quote has been provided to install a 16x25x1 filter rack.Blower motor was fully operational not showing any signs of being intermittent or dropping out.Blower wheel was inspected finding it to be dirty when a blower wheel gets dirty it minimizes the efficiency of equipment along with places a strain on equipment and parts which shortens the lifespan of both a quote has been provided to clean blower wheel.Also inspected indoor evaporator coil finding it to be dirty which affects the efficiency of equipment a