Job Checkin

Upon arrival inspected 1st floor coil. Found dye trace on U Bend of evaporator coil. Inspected condenser coil. Remove fan motor to thoroughly check coil. Did not find any signs of dye trace @ condenser coil at today’s inspection. Explained to customer the possibility of dye showing up @ a later time. Condenser dye search is inconclusive @ the moment. System was ran and checked for normal operation. Whoever customer is aware that he needs to replace evaporator coil. Today’s pressure reading: Low side 125psi / High side 250psi Office to follow up to provide customer with a quote to replace his 1st evaporator coil View visual findings from this job here - https://visionshare.xoi.io/?id=XA-FA02-2A7FB89A75D2420AAC561A2C3C0A28E1