View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-1CBE0DC00AEE4271BF1D422760F67B72 At arrival The customer explained to me what her heating issues are in the home… When they ask for Heat from both the first and second floor thermostats- The fan does not turn on. They need to manually turn the fan on from the thermostat to push the heat out of the system. Customer has a high efficiency, Lochinvar gas water boiler with three Unico Hydro air handlers The first and second floor thermostats are nest thermostats Call for heating from the thermostat- Confirm that the zone valves open at the boiler sending hot water to the Hydro coils, but the blower motors do not turn on. Confirm there is no call for fan at the unit. Check configuration in pro set up- Configure the thermostat thermostats to turn on the fan with a quote for Heat- Show customer Cycle heating on and off multiple times on the first and second floor With customer- The blower motors are responding wi