11 Kimball Place
Mount Vernon, NY 10550
914-793-7700

Job Locations
for new rochelle, ny


Map of New Rochelle NY
Mark E.

Mark E.


Job Checkin

View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-0E7AA2711B704707AB86C2D1B60B7ED5 Customer has no heat on the first floor: confirm that honeywell thermostat is calling for heating check hydro air handler in basement- blower is on and running but hydro coil is cold confirm that there is no call at the taco panel for the circulator pumps running to turn on confirm that there is control is not closing T T to engage the pump bad control board- customer approved repair and board is in stock on van shut power to air handler disconnected all electrical from control board and removed bad board from electrical panel installed and secured brand new board in place connect and secure all electrical back to control board and review all connections before returning power call for heating at thermostat- confirm T T is closed, taco panel getting call for heat, circulator pump is on and running, hydro coil hot and blower motor is on and running- normal operations cycl