View visual findings from this job here - https://visionshare.xoi.io/?id=XA-DE27-9D79B12AFD3F49C683B306A5ED72919C Review customers duct work on the second floor: * The customer states that arrival that she had a different company at her home, performing a maintenance where she was told that the static pressure on the second floor system was too high and overtime could cause failure to the components * At arrival I did confirm that the air filters were clean and clear as well as the coils The customer has geothermal heat pumps heating and cooling the entire home * Had the customer call for heating from the thermostat and raise the temperature so it engaged stage two heating * I performed a static pressure test on the ductwork supply side, where the previous technician had made a hole for access * With the customer performed the static pressure test where it was only reading 0.50-0.55 WG Which is in the accepted range from the manufacturer * The previous technician stated that the sta