View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-ED2A042B0F4146709357DE88F065D691 Customer has no Heat coming from the Amanda Heat pump condenser with Unico Air handler: At arrival confirmed that the thermostat is calling for heating The indoor unit is on and running, but blowing cold air Check the outdoor condensing unit Found the system off on an error for locked tripped Compressor Confirmed that there is 24 V going out to the condenser to call for heat pump Contact is not being pulled in Found the condenser coil completely restricted on all four sides Clean the condenser coil to allow proper airflow and operations Reset the core diagnostic board and the condenser is on and running Cycle system on and off multiple times from the thermostat, confirming that the condenser turns on and off each time with a call for Heat Monitor operations and check airflow and temperature splits- okay System is back up and running- No failures or faults The system pres