View visual findings from this job here - https://visionshare.xoi.io/?id=XA-213F-169A3DBF2BB84393A0C45C1E1DADF8E4 Perform maintenance on Burnham Alpine high-efficiency water boiler with two Unico Hydro air handlers: GAS WATER BOILER: shut power to boiler removed boiler door to access components disconnected and removed dirty condensate trap disconnected and removed flame rod and spark igniter Cleaned both the flame rod and spark igniter with copper bristle brush and polished clean with steel wool- Reinstalled and secured all connections Chemically sprayed and brushed condensate trap, clean and clear, Flush and prime with freshwater Recommended neutralizer mineral replacements- The customer had them on site Disconnected condensate pump and dumped old minerals / Washed and brushed inside of pump, clean and clear / Prime with freshwater and install new neutralizer minerals provided by customer Reassemble pump and drainage- Support the three-quarter PVC Pipe that is leaving the boiler a