View visual findings from this job here - https://visionshare.xoi.io/?id=XA-A243-0CD691CEAF644C76B8E7678EF1223885 Customer has a leak from steam piping and possibly a cracked heat exchanger on steam boiler: At arrival, the thermostat is satisfied at temperature and the boiler is off check the steam boiler and piping the customer Pointed out two different locations where he states the steam piping is 100% leaking Before turning on the boiler, Test the low water cut off and automatic water fee to confirm normal operations- okay Then inspected heat exchanger from both the top and bottom- okay Fill the steam boiler up all the way filling past the sight glass to test the heat exchanger for leaks- none drain boiler back down to normal level- had to drain 4 - 5 gallon buckets before water level is back in sight glass call for heating and test operations- boiler fires normally monitor system and identify leaking areas. To repair these leaks the steam headed is going to need to be cut and re