No cooling, blower is running, but the condenser is not. Getting 24 V to defrost control but contactor is not pulling in. Getting 24 V across high-pressure switch. Ohmed out high pressure switch and getting open switch. Bypassed high-pressure switch by moving the purple wire to contactor to get cooling for now. Checked refrigerant pressures and refrigerant pressures are within factory specs. Ordered pressure switch and part should take a week or so to get in. Needs to be ordered from factory. System is cooling and running OK at this time.