Job Checkin

Preformed system checked on up and Downstairs system both units are in need of a filter change. The upstairs system condenser fan motor locked up causing the compressor to overheat and no cooling to occur, this also over worked the Downstairs as its return is also upstairs. Had to go to trane to get the cfm. Replacement went smoothly but the compressor was still out on thermal overload, after running water over it to cool it off the system began to run normally. I couldn't get super accurate refrigerant readings dur to dirty filters, the upstairs return air being over 80 degrees, and the outside unit being soaked with water. Though the temperature split was 16 degrees difference between return and supply air. So the customer will continue to monitor system performance At this time found no issues with system performance.