577 Sterling Drive
Richardson, TX 75081
972-591-0199

Job Locations
for wylie, tx


Map of Wylie TX
Russ T.

Russ T.


Job Checkin

Came out for 2 system tuneup. Rheem 2.5 ton system checks out great. 5 ton system is 700 cfms short on return air. There is already a 18 inch duct in place which allows 1300cfm 5ton system needs an additional 14 inch duct to make it perfect. This potentially endangering the metering device and compressor also the blower motor