Homeowner had errors pop up on their 1050 thermostat control showing ERR. 184.03 LSSP CLG CO numerous times. Problem description: low suction pressure protection in cooling mode (5 minute soft lockout) **suction pressure less than 50 PSIG **5 occurrences within approx. 5 hours will result in universal hard lockout (184.08) Possible Casues: Low charge EEV pump down Low side restriction Press transducer out of calibration or failure Checked system in test mode and let stabilize for 20 minutes System is operating at this time as designed (see MQ photo) No none issues at this time outside of a low cooling evaporator load (below 68*) inside temperature. Showed Mike and explained we cannot start replacing parts unless we know what is wrong and agreed with he assement Mike had to leave for the airport Deployed all air probes, line temps and pressure probes connected to measure quick Cycled through thermostat control for any other errors and none present except where the power was cycle