Arrived to indoor unit running, went outside saw contactor was pulled in but outdoor unit was not starting, checked voltage at contactor no voltage, checked voltage at disconnect no voltage. Checked breaker, breaker had been flip reset breaker and powered up outdoor unit. System turned on however pressures were high, and compressor amp draws were high, removed leaves from around outdoor unit and rinsed outdoor coils to determine reason compressor over amping, pressures dropped to normal and compressor is still over amping compressor is beginning to fail. System is cooling at this time.