DCM1: AC complete, replaced 20x20x1 filter. System is functional however is not operating within manufacturer specifications at this time due to indoor capacitor being out of range (10+-10% 7.9) and outdoor fan side capacitor being out of range (45/5+-10% 43.2/3.2). Refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions. Due to age of system multiple part failure is possible at anytime. Photos and maintenance checklist attached.