Service Call Summary – Vibrations from Water Pipes Date: 10 December 2025 Customer: Rock & Mrs. Payne Technician: Shawn Customer Concern Customer reported vibrations/noises coming from the water pipes throughout the home that have worsened over the past 1–2 years. Findings Pressure Regulating Valve (PRV) Existing PRV manufactured in 2012 (13 years old) Incoming static pressure drops to ~35 psi (low), but builds to excessive pressure overnight Classic symptom of a failing/diaphragm-deteriorated PRV Water Heater Manufactured September 2011 (14 years old) Significant sediment buildup causing audible percolation/boiling noises during heating cycle No leaks observed at this time No thermal expansion tank installed (required when a PRV is present) Toilets Upstairs hall bathroom: Toilet running due to soap dispenser physically blocking the flapper Master bathroom: Fill valve failed and allowing tank to continuously run (common secondary symptom of fluctuating pressure from bad PRV)

Service Call Summary – Vibrations from Water Pipes
Date: 10 December 2025
Customer: Rock & Mrs. Payne
Technician: Shawn

Customer Concern
Customer reported vibrations/noises coming from the water pipes throughout the home that have worsened over the past 1–2 years.

Findings


Pressure Regulating Valve (PRV)

Existing PRV manufactured in 2012 (13 years old)
Incoming static pressure drops to ~35 psi (low), but builds to excessive pressure overnight
Classic symptom of a failing/diaphragm-deteriorated PRV


Water Heater

Manufactured September 2011 (14 years old)
Significant sediment buildup causing audible percolation/boiling noises during heating cycle
No leaks observed at this time
No thermal expansion tank installed (required when a PRV is present)


Toilets

Upstairs hall bathroom: Toilet running due to soap dispenser physically blocking the flapper
Master bathroom: Fill valve failed and allowing tank to continuously run (common secondary symptom of fluctuating pressure from bad PRV) Service Call Summary – Vibrations from Water Pipes
Date: 10 December 2025
Customer: Rock & Mrs. Payne
Technician: Shawn

Customer Concern
Customer reported vibrations/noises coming from the water pipes throughout the home that have worsened over the past 1–2 years.

Findings


Pressure Regulating Valve (PRV)

Existing PRV manufactured in 2012 (13 years old)
Incoming static pressure drops to ~35 psi (low), but builds to excessive pressure overnight
Classic symptom of a failing/diaphragm-deteriorated PRV


Water Heater

Manufactured September 2011 (14 years old)
Significant sediment buildup causing audible percolation/boiling noises during heating cycle
No leaks observed at this time
No thermal expansion tank installed (required when a PRV is present)


Toilets

Upstairs hall bathroom: Toilet running due to soap dispenser physically blocking the flapper
Master bathroom: Fill valve failed and allowing tank to continuously run (common secondary symptom of fluctuating pressure from bad PRV)