DCM13: Heat complete, need to return to repair systems 11, 12 and 13 and finish maintenance on office systems. Replaced (11) 20x20x1 and (2) 16x20x1 filters. Set thermostats to 62 heat. All other systems are fully functional and operating within manufacturer specifications. System #11 : System had tripped breaker at outdoor unit, need to replaced 40 amp GE two pole bolt in breaker System #12 : system is functional however is not operating within manufacturer specifications at this time due to outdoor capacitor being low 70+5 reading 50.2/2.2. Will need to replace capacitor for system to operate within manufacturer specifications. System #13: capacitor is low 70 + 5 reading 4.3/5 causing the compressor to not start. Will need to replace capacitor for system to operate properly.