Arrived to system in cool thermostat set to 70 reading 74. Found system is low 3-4lbs of R410A. Found multiple leaks in indoor coil (video attached). System is 9 years old and is no longer under warranty. Spoke with Scott and he approved repair. He requested a comfort advisor to give quote on replacing complete system and quote to replace indoor coils out of warranty. Added 4lbs 6oz of R410A, system is now operating properly and refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions at this time. Leak is not repaired, system will continue to leak refrigerant at an unknown rate. System is 6lbs