Unwired fan motor and removed existing fan motor from blades. Ensured motors where the same with matching RPMs 910 and 208-230v variable speed. Installed new condenser fan motor and wired in per manufacturer specifications. Tested fan motor, fan is pulling appropriate amount of amps 1.1. Checked refrigerant pressures and temperatures they are appropriate for indoor and outdoor weather conditions. Condenser fan motor is operating properly at this time. 2 year part and labor on condenser(outside) fan motor. Price also includes returning part to manufacture.