Client called us out today due to them having some drain backup issues. Client is on septic and had some work done under garage floor replacing some old cast iron pipe with pvc. When they did that, they added a cleanout in garage floor. We ran the camera down the cleanout all the way to the tank and determined the septic tank is full and needs pumped. The remaining cast iron pipe does look rough with some channeling but not backed up. Checked water pressure and it was high at 120 psi. Safe range is 50-79 psi. We cut out the old pressure regulator and replaced it, moving it further back on the line because the water heater was not regulated before. Added new ball valve and pressure regulator as well as a couple pipe supports. Turned water back on and tested, no leaks. Home pressure is now around 60 psi. 1 yr warranty on pressure regulator.