Jorge C.

Jorge C.


Job Checkin

Performed diagnostic on 2 2008 York systems. Homeowner states that she is having some issues with both of her units. She is good friends with Jay and will be signing up on ESA maintenance program today. Homeowner states that her system for the bedrooms feels like sometimes air is not coming out as cold as it used to. She also stated that her kitchen system is working periodically as well. Cycled both units for cooling. Indoor units both kicked on and are blowing air. Bedroom system kicked on normally. Refrigerant pressures are within range and system is producing proper temperature split. Checked all electrical and system components. Secondary motor control is within range as well as compressor hard start kit. Amp draws are within range for both compressor and condenser fan motor. Primary motor control is completely full of ants inside the contact points. Kitchen system compressor is not kicking on. Checked unit electrical and components. Primary motor control was also full of ants and