No cool, client says it wasn’t getting below 90° at home. Upon arrival thermostat was off. Turn thermostat to cool and cycled AC system. Everything seemed to be working. OK did a complete evaluation of a C system. Checked the temperatures and pressures. Everything within manufacture specs. Did notice that the compressor had high start up amps. Recommended installing a hard star kit in signing up for membership. Client declined recommendations at this time. System is up and running and cooling at this time.