Brennan G Today I visited to inspected and diagnose all 3 AC systems after a lightning strike had caused 2 of 3 systems to stop cooling. System#1: 3.0ton heatpump , serves leftside 2004 Trane Condenser, 2010 Goodman air handler. Air handler is locted in "playroom" closet. Horizontal This system is running but not cooling and needs major repairs preformed that are unrelated to the lightning strike. I found this system is low on refrigerant and a visual sign of a refrigerant leak on the evaporator coil. The condenser coil is dirty and corroded. Burnt contact relay. Does not have a primary drain pan Float sensor( has caused water damage in the past). Dirty blower wheel, dirty drain line. High compressor start amps. Due to age , overall condition and total repair cost , repairs are not recommended System #2: 4.0ton heatpump. Serves upstairs, 2-zone system. 2004 trane condenser, 2004 trane air handler. Air handler is locted in attic, horizontal This system needs a new condenser fa