The first time I came out here, the machine had a small clog in the line. Customer had a little bit of concerns about the machine, not cooling correctly, so I added just a tad bit of refrigerant to see if it would change degrees the degrees only went up by maybe one when I came back today there was water everywhere in the machine. The EVap coil pan is completely caked up and is not allowing water to flow out of it. Also, they return Plenum in the coffin boxes is completely detached from the coffin box and is allowing a lot of attic air to mix along with insulation being sucked into the EA coil. The vape coil needs to be pulled and cleaned Along with the blower wheel that is caked with growth and the return Plenum inside the coffin box needs to be reattached along with re-insulating the coffin box.