Arrived on site to diagnose a no cooling 2018 Goodman system. Condenser located in back alley. Furnace and evaporator coil located in up stairs closet. Client cycled cooling mode on. He stated just recently these few days system stoped cooling and condenser would not operate. Inspect indoor unit and is operational. Condenser did not turn on. Found condensate float switch was tripped due to system having high air flow pressure in system and some water was pushed in secondary line were condensate switch is at. Cleared primary line and is good. Water tested and is good and draining. Tested drain pump and it’s all good. Checked static pressure is was high on supply side as there is a air flow restrictions. Advised client due to being a up flow we can not add more return but could upsize supply duct to provide better air flow. Used rage to dry bit of water that’s was in secondary and had system running and system did has yet to Tripp safety switch since. Checked refrigerant pressure and