Customer called about over voltage at some outlets and under voltage at others. Arcing can be heard inside the meter base. Opened main electric panel check voltages. Found issue is intermittent. Home currently has original meter base with a Federal Pacific panel in the master bedroom closet as well as an older QO panel next to the meter. Feeder wires are double lugged inside the meter base and burning up. 1. Pull all city permits and inspection 2. Replace burnt up meter base (lifetime warranty) 3. Relocate all circuits to outside next to meter and condense into 1 panel 4. Install weatherproof 200 amp main breaker next to meter (lifetime warranty) 5. Install grounding system 6. Install whole home surge protector - 108k amps protection (lifetime warranty) 7. Install GFCI protection for all required wet locations 8. Install customer supplied battery powered bluetooth interconnected smoke detectors in bedrooms and hallways (Free) Marco@calltoptech.com 682-262-5759 Replaced and reloca