Arrived onsite for ac maintenance on 1 units. tTurn AC on to confirm operation. Checked all electrical. Chemically Cleaned outside unit, measured pressures for 410a at 100/235psi with 6 degree sub cooling with outside temperature at 65 degrees. Measured temperature drop at 25 degrees. Cleaned evaporator coil and blew out condensate line. System running as it should.