5558 Berkshire Valley Road STE 6
Oak Ridge, NJ 07438
(973) 838-3200

Our Top Cities


Local Reviews
for glen rock, nj

Rated 5.0 out of 5 stars based on 10 customer reviews

Quick response


Response from Climate Plus, LLC:

Thank you Wendy for the 5-star review! We're thrilled to receive such positive feedback. At Climate Plus, we pride ourselves on delivering exceptional service quickly and efficiently. If you ever need further assistance, we're just a call away. Your satisfaction is our top priority!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Very professional

Jack responded quickly, identified the problem, and fixed it in a few hours.


Response from Climate Plus, LLC:

Thank you for your review Jeff! We're glad to hear that Jack provided very professional service. Responding quickly, identifying the problem, and fixing it efficiently are key aspects of our service. If you need any further assistance, just reach out and we will be there! -Joe

  • Overall Experience
  • Quality
  • Price
  • Convenience

Terrific servicemen

Terrific service! Thx


Response from Climate Plus, LLC:

Thanks Judy! It is a pleasure to have you as a customer. -Joseph

  • Overall Experience
  • Quality
  • Price
  • Convenience

Service with a smile


Response from Climate Plus, LLC:

Thanks Wendy! Happy to provide you with the best service here at Climate Plus! -Joseph

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service

Always great service with a smile

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great service and helpful gentlemen


Response from Climate Plus, LLC:

Thank you so much for your 5-star review! We will share this with the team to let them know to keep up the amazing work.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Quick and great service!


Response from Climate Plus, LLC:

We’re so happy you loved your experience and can’t wait to have you back for your next service appointment.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for glen rock, nj

Jack B.

Jack B. Job Checkin

rrived onsite for maintenance for one gas fired steam boiler. Requested the customer turn on the thermostats up to heat and confirm operation of the boiler. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment. Observed significant rust on the burners; looked for leaks but did not observe a leak. homeowner stated they had water issue in the past. Performed a visual inspection of all electrical and inspected all external water components such as automatic water feeder, fill valve, backflow preventer and pressuretrol. Did not observe discoloration in site glass. Confirmed water level on site glass is within specification. Confirmed site glass valves are operational and opened. Confirmed everything is operating and heating properly at this time.

rrived onsite for maintenance for one gas fired steam boiler.

Requested the customer turn on the thermostats up to heat and confirm operation of the boiler. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment. Observed significant rust on the burners; looked for leaks but did not observe a leak. homeowner stated they had water issue in the past. Performed a visual inspection of all electrical and inspected all external water components such as automatic water feeder, fill valve, backflow preventer and pressuretrol. Did not observe discoloration in site glass. Confirmed water level on site glass is within specification. Confirmed site glass valves are operational and opened. Confirmed everything is operating and heating properly at this time.

Jack B.

Jack B. Job Checkin

Arrived onsite for heating maintenance 1 gas fired furnace located in basement. Ask customer to turn heat on and confirmed operation. Changed filter 16x25x1. Brushed and Wiped down blower cabinet and gas burners. Burners fired and are in good working order. Observed visual impingement detected. Checked electrical. Measured .5 amps on the hot surface igniter. Cleaned and Measured 4.9 micro amps on the flame sensor. Measured 135 degrees at the air supply and 80 degrees at the return for 55 degree heat rise within specifications. Furnace is operating as it should but showing its age.

Arrived onsite for heating maintenance 1 gas fired furnace located in basement. Ask customer to turn heat on and confirmed operation. Changed filter 16x25x1. Brushed and Wiped down blower cabinet and gas burners. Burners fired and are in good working order. Observed visual impingement detected. Checked electrical. Measured .5 amps on the hot surface igniter. Cleaned and Measured 4.9 micro amps on the flame sensor. Measured 135 degrees at the air supply and 80 degrees at the return for 55 degree heat rise within specifications. Furnace is operating as it should but showing its age.

Gianna M.

Gianna M. Job Checkin

Arrived onsite for no hot water form indirect boiler and maintenance for one gas fired high efficiency boiler. Found boiler off due to low water pressure. Used fast fill valve to bring pressure to 19 psi. Turn on the thermostats up to heat and confirm operation of the boiler and each zone valve. Turned the boiler off and removed heat exchanger cover. Cleaned heat exchanger. Cleaned the flame sensor and igniters. Performed a visual inspection of all electrical and inspected all external water components such as the exp tank, fill valve, backflow preventer and the circulator pump. Clear condensate lines. Confirmed system is operating and heating properly at this time.


Jack B.

Jack B. Job Checkin

Arrived onsite for no hot water form indirect boiler and maintenance for one gas fired high efficiency boiler. Found boiler off due to low water pressure. Used fast fill valve to bring pressure to 19 psi.

Arrived onsite for no hot water form indirect boiler and maintenance for one gas fired high efficiency boiler. Found boiler off due to low water pressure. Used fast fill valve to bring pressure to 19 psi.

Gianna M.

Gianna M. Job Checkin

Arrived on site for black stuff shooting out of unit. The black stuff shooting out of the ductless unit is bacterial Growth. Sprayed non rinse evaporator cleaner on coils. Inform the customer that the bacterial growth is coming from the blower wheel. Inform them that we need to take the blower wheel out of the system which is a several hour work to appropriately try to get rid of the growth. Customer did state that they have no issues with Cooling so unit is working fine aside from having bacterial growth. Used a diluted chemical and cleaning wipes to get rid of the growth on the lip of the unit the best that I could.

Arrived on site for black stuff shooting out of unit.
The black stuff shooting out of the ductless unit is bacterial Growth.
Sprayed non rinse evaporator cleaner on coils.
Inform the customer that the bacterial growth is coming from the blower wheel. Inform them that we need to take the blower wheel out of the system which is a several hour work to appropriately try to get rid of the growth. Customer did state that they have no issues with Cooling so unit is working fine aside from having bacterial growth. Used a diluted chemical and cleaning wipes to get rid of the growth on the lip of the unit the best that I could.

Gianna M.

Gianna M. Job Checkin

Arrived on site for maintenance. Customer stated no issues with the unit as I'm late. Customer led me to the air handle that is located in basement. Customer stated that they used to have a leak by the condensation pump, customer cleared out the PVC with a brush.

Arrived on site for maintenance. Customer stated no issues with the unit as I'm late. Customer led me to the air handle that is located in basement. Customer stated that they used to have a leak by the condensation pump, customer cleared out the PVC with a brush.

Gianna M.

Gianna M. Job Checkin

Arrived on San Bruno cooling, replacing blower motor. Once getting on site went to the Attic the air handler. Made sure the unit was shut off to be able to perform on the unit safely. Opening up the panel the unit and unscrewing the screws that are attached to the casing. Took out the blower motor and separated the blower motor from the fins/casing. Took the fins and casing outside to spray down with chemical and water. At the completely cleaning the casing of the blower motor with the fins make sure they were completely dry before putting it back together and bringing it back up to the Attic.

Arrived on San Bruno cooling, replacing blower motor. Once getting on site went to the Attic the air handler. Made sure the unit was shut off to be able to perform on the unit safely. Opening up the panel the unit and unscrewing the screws that are attached to the casing. Took out the blower motor and separated the blower motor from the fins/casing. Took the fins and casing outside to spray down with chemical and water. At the completely cleaning the casing of the blower motor with the fins make sure they were completely dry before putting it back together and bringing it back up to the Attic.

Jack B.

Jack B. Job Checkin

Arrived onsite to install wet switch and confirmed proper operation of the air conditioning system. Installed wet switch. Wired it into the system. Confirmed operation of the wet switch. Confirmed operation of the air condition system. System working as it should.


Gianna M.

Gianna M. Job Checkin

Arrived on site for 2c maintenance Turned on both thermostats (2 Tstats. One oer unit) Went to attic to check on evaporator coils and check Metering device: Piston. Filter was a little dirty but wasnt due, was changed 3 weeks before todays visit. Went to basement and inspected evaporator coils. Piston. Went outside and determined small unit is upstairs. Bigger is down stairs. Washed unit inside out with chemical and water.

Arrived on site for 2c maintenance
Turned on both thermostats (2 Tstats. One oer unit)
Went to attic to check on evaporator coils and check Metering device: Piston.
Filter was a little dirty but wasnt due, was changed 3 weeks before todays visit.
Went to basement and inspected evaporator coils. Piston.
Went outside and determined small unit is upstairs. Bigger is down stairs.
Washed unit inside out with chemical and water.

Gianna M.

Gianna M. Job Checkin

Afternoon Arrival; Comfort Club 1C- Customers outside unit is not turning on. Unit from 2021. Customer is aware of diagnostic and denied partner plan

Afternoon Arrival; Comfort Club 1C- Customers outside unit is not turning on. Unit from 2021. Customer is aware of diagnostic and denied partner plan

Gianna M.

Gianna M. Job Checkin

Afternoon Arrival; Cozee Club Customer- Having issues with cooling, every time I ask her what areas of the house she says theres a new part that isn't cooling. Saying that unit rattle sometimes, she just had a maintenance in May. Nothing there looks abnormal rattling wise. She also mentioned that she needs an estimate on a bulb.

Afternoon Arrival; Cozee Club Customer- Having issues with cooling, every time I ask her what areas of the house she says theres a new part that isn't cooling. Saying that unit rattle sometimes, she just had a maintenance in May. Nothing there looks abnormal rattling wise. She also mentioned that she needs an estimate on a bulb.

Gianna M.

Gianna M. Job Checkin

Arrived on site for no cooling on the top floor AKA attic. Check temperature split with probes temperature split with about 1° of difference. Disconnected the float switch. After disconnecting the float switch the temperature split peaked at 23° difference. Installed a new float switch, temperature split dropped back to two to three degrees. Left the float switch there unwired to the air handler and temperatures split increase again 20° difference. Made customer aware that there is no float switch in the unit and that we will contact him for the replacement.


Jack B.

Jack B. Job Checkin

Refrigerant is used in an air conditioning system to help create the cool air and remove humidity. Due to leaks, system repairs or annual testing additional refrigerant may need to be added. If a system requires refrigerant to be added it is a sign that it may be leaking. We include a non-intrusive electronic leak test at the time of visit. We also recommend adding leak stop/dye to help slow the leak down and find it in the future.


Gianna M.

Gianna M. Job Checkin

Arrived on site for A/C maintenance . Customer lead me to thermostat and Air handler. System was already on. No issues. Changed filter of unit. Checked out blower wheel and evaporator coils, everything was good as new. Condenser was running with no issues. Washed down condenser with chemical and water. Checked pressures of unit, and also used temperature probes.

Arrived on site for A/C maintenance .
Customer lead me to thermostat and
Air handler.
System was already on.
No issues.
Changed filter of unit.
Checked out blower wheel and evaporator coils, everything was good as new.
Condenser was running with no issues.
Washed down condenser with chemical and water.
Checked pressures of unit, and also used temperature probes.

Jack B.

Jack B. Job Checkin

Replace the media filter for a high performance mechanical filtration system, includes wiping down of the filter cabinet.

Replace the media filter for a high performance mechanical filtration system, includes wiping down of the filter cabinet.