5558 Berkshire Valley Road STE 6
Oak Ridge, NJ 07438
(973) 838-3200

Our Top Cities


Local Reviews
for franklin lakes, nj

Rated 5.0 out of 5 stars based on 2 customer reviews

Fast and Friendly service!


Response from Climate Plus, LLC:

Hi Michael. Glad we were able to provide you with the prompt and friendly service that you deserve. -Joe

  • Overall Experience
  • Quality
  • Price
  • Convenience

Easy to Work With!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for franklin lakes, nj

Jack B.

Jack B. Job Checkin

Arrived onsite for a no heat service call on master bedroom system. Performed diagnostic on system. Found a loose wire connecting the outdoor system to the indoor system. Reattached wire and system began cooling. Refrigerant levels 410a seem good.


Jack B.

Jack B. Job Checkin

Arrived onsite to clean ac systems to remove organic growth and ad Indoor Air Quality solution to scrub the air. Opened all indoor air handlers. Removed blower fan cage from compartment. Used evaporator cleaners and cleaned entire inside compartment of each air handlers. Sprayed each evaporator coils. Removed any dust from the evaporator coils. We will return to add heat shield to the UV light system. To protect plastic flex ductwork, switch the UV light off for the moment.

Arrived onsite to clean ac systems to remove organic growth and ad Indoor Air Quality solution to scrub the air. Opened all indoor air handlers. Removed blower fan cage from compartment. Used evaporator cleaners and cleaned entire inside compartment of each air handlers. Sprayed each evaporator coils. Removed any dust from the evaporator coils.
We will return to add heat shield to the UV light system. To protect plastic flex ductwork, switch the UV light off for the moment.

Jack B.

Jack B. Job Checkin

Arrived onsite for issues with heating system. Homeowner is hearing the boiler click on and off constantly. Performed diagnostic. Had all thermostat turned on. Confirmed operation of the boiler. Confirmed operation of each zone. Boiler turned fired up and shut down at 180 degrees as designed and then came back on at 160 degrees as designed. All zone heated. All baseboard heated. Concluded that second floor bedrooms above garage may have had a frozen pipe stopping the flow of water. Homeowner will continue to observe that zone. Note the water heater is not providing the same about if hot water as it did in the past. Noted during maintenance they the water heater is past the age of replacement and should be replaced. Recommend on demand water heating system. Also, discussed the renovation to the shore house. Recommend adding in demand water heater there and recommend upgrading to heat pump system.

Arrived onsite for issues with heating system. Homeowner is hearing the boiler click on and off constantly. Performed diagnostic. Had all thermostat turned on. Confirmed operation of the boiler. Confirmed operation of each zone. Boiler turned fired up and shut down at 180 degrees as designed and then came back on at 160 degrees as designed. All zone heated. All baseboard heated. Concluded that second floor bedrooms above garage may have had a frozen pipe stopping the flow of water. Homeowner will continue to observe that zone. Note the water heater is not providing the same about if hot water as it did in the past. Noted during maintenance they the water heater is past the age of replacement and should be replaced. Recommend on demand water heating system. Also, discussed the renovation to the shore house. Recommend adding in demand water heater there and recommend upgrading to heat pump system.

Jack B.

Jack B. Job Checkin

Arrived onsite for maintenance for one gas fired boiler. turned the thermostats up to heat and confirmed operation of the boiler and each zone valve. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment. Performed a visual inspection of all electrical and inspected all external water components such as the exp tank, fill valve, backflow preventer and the circulator pump. Completed combustion test. At customer’s request installed 4 digital thermostats. Confirmed proper operation of all thermostats.

Arrived onsite for maintenance for one gas fired boiler. turned the thermostats up to heat and confirmed operation of the boiler and each zone valve. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment. Performed a visual inspection of all electrical and inspected all external water components such as the exp tank, fill valve, backflow preventer and the circulator pump. Completed combustion test. At customer’s request installed 4 digital thermostats. Confirmed proper operation of all thermostats.

Jack B.

Jack B. Job Checkin

Arrived onsite to install gas shut off isolation valve behind clothing dryer. This is needed so homeowner can have their new dryer installed.

Arrived onsite to install gas shut off isolation valve behind clothing dryer. This is needed so homeowner can have their new dryer installed.

Jack B.

Jack B. Job Checkin

Arrived onsite to install gas shut off isolation valve behind clothing dryer. This is needed so homeowner can have their new dryer installed.

Arrived onsite to install gas shut off isolation valve behind clothing dryer. This is needed so homeowner can have their new dryer installed.

Jack B.

Jack B. Job Checkin

Arrived onsite for maintenance for one gas fired boiler. Turn on the thermostats up to heat and confirm operation of the boiler and each zone valve. Only found one zone valve but it was operational. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment. Performed a visual inspection of all electrical and inspected all external water components such as the exp tank, fill valve, backflow preventer and the circulator pump. System working as it should. Performed dryer vent cleaning. Replaced 2 air scrubber bulbs by Argus. Please note 75 gallon water heater is due for replacement. It is manufactured in 2010. At 14 years old it is near failure which could be leaking and flooding the basement.

Arrived onsite for maintenance for one gas fired boiler. Turn on the thermostats up to heat and confirm operation of the boiler and each zone valve. Only found one zone valve but it was operational. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment. Performed a visual inspection of all electrical and inspected all external water components such as the exp tank, fill valve, backflow preventer and the circulator pump. System working as it should. Performed dryer vent cleaning. Replaced 2 air scrubber bulbs by Argus. Please note 75 gallon water heater is due for replacement. It is manufactured in 2010. At 14 years old it is near failure which could be leaking and flooding the basement.

Jack B.

Jack B. Job Checkin

Arrived onsite for heating maintenance 4 gas fired furnaces with 2 humidifiers. Turned on all thermostats and Confirmed operation of all heating systems Basement Furnace Left: Turned on humidifier and set to winter. Panel 45 in good shape. Brushed and Wiped down furnace blower cabinet and gas burners. Burners fired and are in good working order. No visual impingement detected. Checked electrical. Cleaned flame rectification system. Measured 50 degree heat rise. System is operating as it should. Basement Furnace Right: turned on humidifier and set to winter. Panel 45 in good shape. Brushed and Wiped down furnace blower cabinet and gas burners. Burners fired and are in good working order. No visual impingement detected. Checked electrical. Cleaned flame rectification system. Measured 47 degree heat rise. System is operating as it should.

Arrived onsite for heating maintenance 4 gas fired furnaces with 2 humidifiers. Turned on all thermostats and Confirmed operation of all heating systems Basement Furnace Left: Turned on humidifier and set to winter. Panel 45 in good shape. Brushed and Wiped down furnace blower cabinet and gas burners. Burners fired and are in good working order. No visual impingement detected. Checked electrical. Cleaned flame rectification system. Measured 50 degree heat rise. System is operating as it should. Basement Furnace Right: turned on humidifier and set to winter. Panel 45 in good shape. Brushed and Wiped down furnace blower cabinet and gas burners. Burners fired and are in good working order. No visual impingement detected. Checked electrical. Cleaned flame rectification system. Measured 47 degree heat rise. System is operating as it should.

Jack B.

Jack B. Job Checkin

Installed new Aprilaire E100 Dehumidifier. Removed failed dehumidifier. Installed new dehumidifier. Connected thermostat controls for external blower motor. Connected ductwork and leveled system. Installed new custom drain pain. Reattached condensate drain line.

Installed new Aprilaire E100 Dehumidifier. Removed failed dehumidifier. Installed new dehumidifier. Connected thermostat controls for external blower motor. Connected ductwork and leveled system. Installed new custom drain pain. Reattached condensate drain line.

Jack B.

Jack B. Job Checkin

Arrived onsite for maintenance for one gas fired boiler. Requested the customer turn on the thermostats up to heat and confirm operation of the boiler and each zone valve. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment: performed a visual inspection of all electrical and inspected all external water components such as the exp tank, fill valve, backflow preventer and the circulator pump. System working as it should.

Arrived onsite for maintenance for one gas fired boiler. Requested the customer turn on the thermostats up to heat and confirm operation of the boiler and each zone valve. Turned the boiler off and removed and cleaned all burners and wiped cleaner the burner compartment: performed a visual inspection of all electrical and inspected all external water components such as the exp tank, fill valve, backflow preventer and the circulator pump. System working as it should.

Jack B.

Jack B. Job Checkin

Basement Furnace System: Turned on the heat and confirmed proper operation. Replaced the 20x25x1 filter and cleaned the blower cabinet and gas burners, which were in good working order with no signs of impingement. Blew out the condensate line for the condensing furnace. Checked electrical components, cleaned the flame sensor, and measured a temperature rise of 52 degrees (73/125). System is functioning properly. The filter cabinet is an older Lennox model with UV light bulbs. Recommended updating it for easier filter changes, but the homeowner is not interested at this time. Also noted that the humidifier is non-operational and suggested replacing it if dry air becomes an issue.

Basement Furnace System: Turned on the heat and confirmed proper operation. Replaced the 20x25x1 filter and cleaned the blower cabinet and gas burners, which were in good working order with no signs of impingement. Blew out the condensate line for the condensing furnace. Checked electrical components, cleaned the flame sensor, and measured a temperature rise of 52 degrees (73/125). System is functioning properly.

The filter cabinet is an older Lennox model with UV light bulbs. Recommended updating it for easier filter changes, but the homeowner is not interested at this time. Also noted that the humidifier is non-operational and suggested replacing it if dry air becomes an issue.

Jack B.

Jack B. Job Checkin

Experience the comfort club difference with our After 2pm Arrival service! Our satisfied customer raves about our prompt attention to her dehumidifier issue, showing E4: NEEDS SERVICE. Trust us to keep your home humidity levels in check. Contact us today for expert service at competitive rates.

Experience the comfort club difference with our After 2pm Arrival service! Our satisfied customer raves about our prompt attention to her dehumidifier issue, showing E4: NEEDS SERVICE. Trust us to keep your home humidity levels in check. Contact us today for expert service at competitive rates.

Jack B.

Jack B. Job Checkin

Experience a seamless 3C EPP late morning/ early afternoon arrival for organic growth assessment. Address cooling issues while alleviating headaches and coughing symptoms. No job notes from last maintenance visit. Contact us today for specialized service under Sheila Scherl's account.


Jack B.

Jack B. Job Checkin

Late Morning, early afternoon Arrival.


Joseph C.

Joseph C. Job Checkin

If your air conditioning unit has been acting up since losing power on Tuesday, contact Climate Plus LLC for a check-up. For After 7:30pm Arrival, EPP 1C, we prioritize emergencies involving pre-school children. If timing doesn't work out, we'll aim for Saturday 9-11am. Customer must confirm availability before office closes.