5558 Berkshire Valley Road STE 6
Oak Ridge, NJ 07438
(973) 838-3200

Our Top Cities


Local Reviews
for paterson, nj

Rated 4.8 out of 5 stars based on 6 customer reviews

excellent service prompt and efficient

very pleased with the prompt efficient service


Response from Climate Plus, LLC:

Thank you for your wonderful feedback! We’re delighted to hear that you were very pleased with our prompt and efficient service. Ensuring excellent service for our customers in Clifton, NJ, is always our top priority. We appreciate your trust in us and look forward to serving you again in the future! Best regards, The Climate Plus Team

  • Overall Experience
  • Quality
  • Price
  • Convenience

prompt excellent service

technician is knowledgeable and efficient


Response from Climate Plus, LLC:

Thank you so much for your review! We're thrilled to hear that you received prompt, excellent service in Paterson, NJ, and found our technician knowledgeable and efficient. Providing top-notch service is our priority, and we're glad we could meet your expectations. If you ever need anything in the future, don't hesitate to reach out! Best regards, The Climate Plus Team

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent service above and beyond

Very happy with Jack Boston’s service in level of expertise


Response from Climate Plus, LLC:

Thank you for your review! We're pleased to hear you received excellent service above and beyond from Jack. His expertise and dedication are what we strive for at Climate Plus. Whether you need HVAC maintenance or any other HVAC services, we're here to help. Best Regards, Joe

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent Service

During the past 8 years I have been using Climate Plus for my company they have great customer service and there technician are always polite and explains the service they will be conducting.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent

Installer came in time. The installation was clean and faster than I expected. Both installers were courteous and a pleasure to have in my home. I appreciated in in person tutorial at the end.


Response from Climate Plus, LLC:

Thank you for sharing your kind words with us. It means the world to us and to our entire team!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Maintenance Service


Response from Climate Plus, LLC:

We are so glad to hear that you had a good experience.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for paterson, nj

Gianna M.

Gianna M. Job Checkin

Arrived onsite for leak test on rooftop AC unit. heating maintenance of 1 boiler, 1 heat strip, and 4 rooftop units. Performed leak on unit that previously diagnosed with low refrigerant in an no AC service call. Upon arrival measured 0 psi for refrigerant on circuit one. Pressurized system with nitrogen heard leak from condenser coil. Upon investigation found the condenser fan blades broke off its rivet. Sliced the coil open, broke a fan motor bracket, and the damaged the other condenser fan blade. Recommend replacing coil, motor mount bracket, and condenser fan motors. Will provide estimate for repair.

Arrived onsite for leak test on rooftop AC unit. heating maintenance of 1 boiler, 1 heat strip, and 4 rooftop units. Performed leak on unit that previously diagnosed with low refrigerant in an no AC service call. Upon arrival measured 0 psi for refrigerant on circuit one. Pressurized system with nitrogen heard leak from condenser coil. Upon investigation found the condenser fan blades broke off its rivet. Sliced the coil open, broke a fan motor bracket, and the damaged the other condenser fan blade. Recommend replacing coil, motor mount bracket, and condenser fan motors. Will provide estimate for repair.

Joseph C.

Joseph C. Job Checkin

Perform the maintenance for the hot water boiler, installed the combustion analyzer and confirmedburnersettings. Cycled and confirmed operation of the circulator pumps, cycled the burner and confirmed that the pilot valve is working correctly and that the main burner is properly igniting. Allowed the boiler to run up to the preset temperature on the aquastat of a 170° and confirmed that it shut down. Allowed the wzter temperature to cool down and verified that the burner properly cycled back on. The boiler and burner are operating properly.

Perform the maintenance for the hot water boiler, installed the combustion analyzer and confirmedburnersettings. Cycled and confirmed operation of the circulator pumps, cycled the burner and confirmed that the pilot valve is working correctly and that the main burner is properly igniting. Allowed the boiler to run up to the preset temperature on the aquastat of a 170° and confirmed that it shut down. Allowed the wzter temperature to cool down and verified that the burner properly cycled back on. The boiler and burner are operating properly.

Joseph C.

Joseph C. Job Checkin

Perform the maintenance for the hot water boiler, installed the combustion analyzer and confirmedburnersettings. Cycled and confirmed operation of the circulator pumps, cycled the burner and confirmed that the pilot valve is working correctly and that the main burner is properly igniting. Allowed the boiler to run up to the preset temperature on the aquastat of a 170° and confirmed that it shut down. Allowed the wzter temperature to cool down and verified that the burner properly cycled back on. The boiler and burner are operating properly.

Perform the maintenance for the hot water boiler, installed the combustion analyzer and confirmedburnersettings. Cycled and confirmed operation of the circulator pumps, cycled the burner and confirmed that the pilot valve is working correctly and that the main burner is properly igniting. Allowed the boiler to run up to the preset temperature on the aquastat of a 170° and confirmed that it shut down. Allowed the wzter temperature to cool down and verified that the burner properly cycled back on. The boiler and burner are operating properly.

Joseph C.

Joseph C. Job Checkin

Performed the maintenance for the gas boiler, confirmed that the zone valves are operating, confirmed burner operation. Allowed the boiler to heat up and confirmed the setting and operation of the limit control. The boiler is operating properly.

Performed the maintenance for the gas boiler, confirmed that the zone valves are operating, confirmed burner operation. Allowed the boiler to heat up and confirmed the setting and operation of the limit control. The boiler is operating properly.

Joseph C.

Joseph C. Job Checkin

Performed the maintenance for the gas boiler, confirmed that the zone valves are operating, confirmed burner operation. Allowed the boiler to heat up and confirmed the setting and operation of the limit control. The boiler is operating properly.

Performed the maintenance for the gas boiler, confirmed that the zone valves are operating, confirmed burner operation. Allowed the boiler to heat up and confirmed the setting and operation of the limit control. The boiler is operating properly.

Joseph C.

Joseph C. Job Checkin

Performed the maintenance for the gas boiler, confirmed that the zone valves are operating, confirmed burner operation. Allowed the boiler to heat up and confirmed the setting and operation of the limit control. The boiler is operating properly.

Performed the maintenance for the gas boiler, confirmed that the zone valves are operating, confirmed burner operation. Allowed the boiler to heat up and confirmed the setting and operation of the limit control. The boiler is operating properly.

Joseph C.

Joseph C. Job Checkin

Arrived onsite for ac maintenance on 1 system . Changed 12x24x1 filter. Turn AC on to confirm operation. Checked all electrical. Chemically Cleaned outside unit, measured pressures for R22 at 60/90psi with 21 degree sub cooling with outside temperature at 43degrees. Measured temperature drop at 16 degrees. blew out condensate line. Performed efficiency test utilizing MeasureQuick. System running but may be slightly low on refrigerant.


Gianna M.

Gianna M. Job Checkin

Arrived on site for no Cooling on the rooftop unit. Opened up the rooftop unit. Notice that the switch of the rooftop unit was not fully on. Forced it to go down to off and then flip it back on unit started up but then shut down. On the control board reason for shutdown was because compressor number one was on low pressure. Put on field pieces to check pressures on unit. Pressures were zero. Have to schedule a leak test,something blew.

Arrived on site for no Cooling on the rooftop unit. Opened up the rooftop unit. Notice that the switch of the rooftop unit was not fully on. Forced it to go down to off and then flip it back on unit started up but then shut down. On the control board reason for shutdown was because compressor number one was on low pressure. Put on field pieces to check pressures on unit. Pressures were zero. Have to schedule a leak test,something blew.

Jack B.

Jack B. Job Checkin

Arrived onsite for warranty repair of fault in the air movement system. Replaced the failed motor and confirmed operation of the system.

Arrived onsite for warranty repair of fault in the air movement system. Replaced the failed motor and confirmed operation of the system.

Joseph C.

Joseph C. Job Checkin

Arrived onsite for ac maintenance on 1 system . Changed 12x24x1 filter. Turn AC on to confirm operation. Checked all electrical. Chemically Cleaned outside unit, measured pressures for R22 at 60/90psi with 21 degree sub cooling with outside temperature at 43degrees. Measured temperature drop at 16 degrees. blew out condensate line. Performed efficiency test utilizing MeasureQuick. System running but may be slightly low on refrigerant.


Jack B.

Jack B. Job Checkin

Arrived onsite to repair broken condensate drain. Removed broken piece and replaced with new drain

Arrived onsite to repair broken condensate drain. Removed broken piece and replaced with new drain

Gianna M.

Gianna M. Job Checkin

Greeted customer upon arrival. No issues with the Units as of late. Checked pressures on RTU, all pressures were good. Condensation drain pipe was broken on one of the machines. Did not have equipment to replace, due for a fix. Customer acknowledged information and signed off

Greeted customer upon arrival.
No issues with the Units as of late.
Checked pressures on RTU, all pressures were good.
Condensation drain pipe was broken on one of the machines.
Did not have equipment to replace, due for a fix.
Customer acknowledged information and signed off

Gianna M.

Gianna M. Job Checkin

Arrived onsite for ac maintenance on 1 system . Changed 12x24x1 filter. Turn AC on to confirm operation. Checked all electrical. Chemically Cleaned outside unit, measured pressures for R22 at 60/90psi with 21 degree sub cooling with outside temperature at 43degrees. Measured temperature drop at 16 degrees. blew out condensate line. Performed efficiency test utilizing MeasureQuick. System running but may be slightly low on refrigerant.


Gianna M.

Gianna M. Job Checkin

Arrived onsite to repair fault in air movement system. Replaced motor that had lubricant system malfunction. Removed bad motor. Disconnected wiring. Removed pulley and attached to new motor. Adjusted pulley. Installed motor. Install belt and adjusted tension. Wired new motor into the system. Confirmed operation.

Arrived onsite to repair fault in air movement system. Replaced motor that had lubricant system malfunction. Removed bad motor. Disconnected wiring. Removed pulley and attached to new motor. Adjusted pulley. Installed motor. Install belt and adjusted tension. Wired new motor into the system. Confirmed operation.