Found 80,000 BTU propane furnace in basement locked out on open rollout switch. Noticed that plastic sight glass was partially melted. Checked for any other open limit switches then tested system operations. Flame is bright orange and fluttering. Severe flame impingement on heat exchanger in front of second burner from left. Flame shape visibly changes when indoor fan kicks on. Inside of PVC exhaust pitch black. Furnace failed combustion test. CO levels in excess of 1000 pp. I explained everything to homeowner. The Heat exchanger and burners need to be replaced. The 3/16” hex plug on gas valve to measure outlet pressure is stripped. I could not remove it to test outlet gas pressure. Gas valve will also need to be replaced. Homeowner was not the homeowner when furnace was installed. We will provide estimate to replace heat exchanger and burners. Recommended replacing furnace. Homeowner wants to schedule consult for furnace upgrade tomorrow. Will be available anytime after 1PM. AC s