520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Job Locations
for malvern, pa


Map of Malvern PA
Joseph D.

Joseph D.


Job Checkin

Installation of a new Vision Pro 8000 Thermostat that is compatible with a Heat Pump system with Emergency heat kit. Install new Vision Pro Thermostat and connect to wireless module. Program thermostat and put system into operation. Test Heat Pump and Emergency Heat on system. Disconnected outdoor module from existing thermostat in “ Wireless device manager” Installed new thermostat programmed and connected outdoor module to new thermostat. No outdoor temperature Heat Pump Droop 3.5° Measured temperature split in cooling 18° Measured temperature rise in heat pump mode 19° Verified electric heat operation Checked wiring and controls, including outdoor capacitor and transformer. Monitored R410A refrigerant pressures in heat and cooling. We installed the 1 heat/1cool thermostat in May 2019. Troy asked that we discuss with management regarding the fact that we had installed a 1 heat/ 1 cool thermostat. The reason it has come to their attention is that there is a new tenant who is maki